Solid-Fuel Industrial Air Heater

HAS.

The hot air you need, with a single burn pot design.

One combustion chamber and one burn pot. The maximum outlet air temperature is 120 °C; higher temperatures require a special design.

Thermal output range75,000–200,000 kcal/h
Airflow rate5,000–15,000 m³/h
FuelSolid fuel
Manufacturing standardEN 13577 | EN ISO 12100 | EN 60204
DESIGN APPROACH

We design your hot air system as a whole.

For HAS, we assess your facility’s heat demand, inlet air temperature, target outlet temperature and required airflow together. We plan the unit as an integrated hot air system, encompassing fuel supply, combustion air, clean air circulation, distribution ducts and the flue connection.

For HAS, we assess the single burn pot in its single combustion chamber together with the unit’s fuel hopper, underfeed screw and combustion air fan. The unit layout accounts for access needed to load the hopper, maintain the stoker, and remove ash and clinker.

We select the circulation fan for the heated clean air, duct routes and distribution points together, based on the required airflow and duct resistance. We address the combustion gas and clean air paths separately. We do not assume that maximum thermal output, maximum airflow and an outlet temperature of 120 °C can all be achieved at the same operating point; requests for higher temperatures are assessed as a special design.

The layout accounts for maintenance door opening, service clearances, ventilation and operator access to the controls. For solid-fuel systems, we also arrange fuel loading and ash removal areas to suit daily use. This allows us to plan the system as a whole, from installation through operation and maintenance. Final capacity, equipment selection and scope of supply are determined for each project and order.

Operation without waterThree-passFire-tube
FUEL FEEDING & COMBUSTION

An operating arrangement
suited to your fuel.

  1. Transfer to the hopper: Fuel from the main coal pit is transferred to the hopper by a conveying screw.
  2. Feeding the burn pot: Fuel in the hopper is fed into the burn pot from below by a screw driven by a geared motor.
  3. Air supply: The fresh air fan supplies air to the combustion zone through the outer air pipe.
  4. Lighting the fuel: The operator lights the fuel in the burn pot.
  5. Combustion with automatic feeding: The screw’s running and pause times are set on the control panel; combustion is maintained by supplying fuel and air.
  6. Ash and clinker formation: After the fuel burns, ash and clinker accumulate around the burn pot.
  7. Cooling: After fuel feeding stops and combustion ends, the system is allowed to cool.
  8. Ash and clinker removal: Once the system has cooled, the operator removes the accumulated ash and clinker.

Small-capacity units do not have a screw conveying coal from the coal pit to the unit’s hopper. This animation explains the system’s general operating principle. Equipment may vary according to the order scope.

TECHNICAL SPECIFICATIONS

Capacity, airflow
and unit construction.

HAS is designed for hot air generation with a three-pass combustion gas channel construction that operates without water. Fuel preparation, combustion and heat transfer are engineered together according to the selected capacity and the facility’s operating conditions.

HAS technical specifications

Capacity and construction

Thermal output range75,000–200,000 kcal/h
Airflow rate5,000–15,000 m³/h
Outlet air temperatureUp to 120 °C; higher temperatures require a special design
ConstructionNo water circuit · Three-pass · Fire-tube
Combustion chamberSingle
Number of burn potsOne
FuelSolid fuel
Fuel feeding / combustionUnderfeed stoker
Solid fuel lower heating value2,000–7,500 kcal/kg
Minimum fuel particle sizeAbove 8 mm
Maximum fuel particle sizeNo more than 35 mm
ManufacturingEngineered to order
Product familyIndustrial Air Heaters

Material standards

Steel plate grades used in manufacturingEN 10025-2 grade S355JR, S235JR
Fire and smoke tubesEN 10217-2 or EN 10216-2 grade P235GH

The series is engineered to order within a thermal output range of 75,000–200,000 kcal/h. These are the limits of a series of units manufactured at different capacities; they do not represent the load adjustment range of a single unit. Final capacity, operating conditions and equipment scope are determined for each project.

Fuel storage and transfer to the hopper

In a stoker-fed system, fuel is stored in the unit’s hopper. Sloped surfaces help the fuel flow towards the feeding point.

Fuel particle size and flow characteristics must be compatible with the feeding system.

Underfeeding by screw and combustion air

Fuel at the hopper outlet is fed from below by a driven screw into the burn pot in the single combustion chamber. Fuel rising through the burn pot reaches the combustion bed. The fresh air fan supplies the air needed to sustain combustion.

HAS has a stoker arrangement with a single burn pot. Feeding and air settings are assessed together according to fuel properties and heat demand.

Combustion bed, ash and clinker removal

In a stoker-fed system, the operator performs the initial lighting; combustion is then maintained by supplying fuel and air. The distribution of the fuel bed and the state of combustion are monitored during operation. Feeding is adjusted to the properties of the fuel used.

Ash forms during combustion; depending on the fuel properties, some ash may form clinker. Removing deposits and keeping air passages clear are part of routine maintenance. Ash and clinker are removed after the system has cooled, in accordance with the operating instructions.

Three-pass combustion gas path

Hot gases produced in the combustion chamber travel through the three-pass combustion gas channels. Reversal sections direct the gases into the next pass, allowing the hot gases to contact the heat transfer surfaces before reaching the outlet.

Heat from the gases is transferred to the clean air flowing on the other side of these surfaces. Heated air and combustion gases are kept in separate flow paths. Cleaning the flue gas passages, checking deposits on heat transfer surfaces and providing maintenance access form part of the operating plan.

Flue gas discharge and auxiliary equipment

After the heat transfer section, combustion gases flow towards the flue connection. Flue and duct dimensions, gas flow rate and system pressure losses are assessed together.

Heating and distributing clean air

The circulation fan moves the air to be heated across the heat transfer surfaces. The heated clean air is sent to the area of use or the process air ducts. This circulating air is considered separately from the combustion air and the gases discharged through the flue.

HAS operates without water; it does not use boiler water as a heat transfer medium. The series airflow range is 5,000–15,000 m³/h. The maximum outlet air temperature is 120 °C; higher temperatures require a special design. Airflow, duct resistance and target temperature are selected together.

Insulation, external cladding and maintenance access

To limit heat loss, hot surfaces are protected with insulation and external cladding suited to the design conditions. Insulation material, thickness and cladding details are determined by the operating temperature and order scope.

Maintenance access is required to the combustion system, heat transfer surfaces and flue connections. Service clearances around the equipment, door opening directions and cleaning areas are considered when preparing the facility layout.

FUEL COMPATIBILITY

The right configuration
starts with your fuel.

Coal and lignite; wood, pellets and suitably sized wood chips; olive pomace and agricultural biomass may be considered when the fuel requirements are met. Fuels containing plastics or unsuitable chemical additives are not accepted. A fuel’s name alone does not establish suitability; its lower heating value, particle size, composition, moisture content and analysis requirements are assessed together.

Coal / LigniteWood / PelletsAgricultural biomass
Open the unit converter
SOLID FUELS · IEA · LOWER HEATING VALUE≈ 1,959–8,431 kcal/kg

Solid fuel and feeding requirements

The product’s current range for project assessment is 2,000–7,500 kcal/kg; this is separate from the typical values in the IEA table. Fuel particle size must be above 8 mm. With stoker feeding, the maximum size is 35 mm.

When lower heating value changes, capacity may change too

All other conditions being equal, more of a fuel with a lower heating value must be burned to meet the same heat demand. Fuel moisture and ash content also affect combustion. The feeding system, combustion chamber, grate, heat transfer surfaces and unit dimensions are therefore determined according to the selected fuel.

At ENORPA, we design the unit around the selected fuel and target capacity. A unit cannot deliver the same thermal output with every solid fuel; achievable capacity is assessed together with the fuel analysis and feeding system.

Explore the heating values of different fuels
ENORPA 360° SUPPORT

From the first conversation throughout your equipment’s life.

We identify your needs together
and support you at every stage.

360°
ENORPA
SUPPORT SHIELD

Comprehensive support in four stages.
One engineering approach.

01 ANALYSIS & CONSULTANCY

The right decision
starts with an expert.

Speak directly with our specialist engineers and receive free advice. Let’s analyse your needs together and identify the right product and capacity for you.

02 CUSTOM MANUFACTURING & SUPPLY

Tailored to your needs.
Built for you.

Let’s turn your technical requirements into equipment made for you. We manufacture and supply your product and the necessary equipment to meet your specific needs.

03 INSTALLATION & COMMISSIONING

We install it. Get it running.
Prepare your team.

We install and commission the products you purchase from us, then train your personnel in their use and operation.

04 LIFETIME TECHNICAL SUPPORT

As your equipment keeps working,
our support continues.

When a fault occurs, we support you through our contracted local service providers or a technical team dispatched from our headquarters, depending on the nature of the issue. We provide technical support throughout the life of your equipment.

FREQUENTLY ASKED QUESTIONS

Before you
decide.

Can HAS be manufactured for an intermediate capacity?

Within the series’ thermal output range of 75,000–200,000 kcal/h, a suitable capacity is engineered by assessing your requirements, fuel and operating conditions together.

Which feeding or combustion system is used?

Underfeed stoker. One combustion chamber and one burn pot. The maximum outlet air temperature is 120 °C; higher temperatures require a special design.

Can 120 °C be achieved at maximum airflow?

These values must not be assumed to occur together at the same operating point. Thermal output, inlet air temperature and airflow are calculated together. Outlet temperatures above 120 °C require a special design.

Which equipment is included in the delivery?

You can choose the air heater body alone, supply with auxiliary equipment, or a solution covering the equipment room. Whether the burner, feeding system, control panel, pumps, fans, flue and other equipment are included is specified individually in the technical proposal.

Are installation and personnel training provided?

Installation, electrical and automation connections, commissioning and operator training are planned according to the project’s service scope. The boundaries of the work are defined in the technical proposal and contract.

When does the warranty begin?

ENORPA-manufactured products carry a 24-month warranty against manufacturing defects. The warranty starts on the actual commissioning date accepted by ENORPA, but no later than two calendar months after delivery. Third-party equipment is subject to the relevant manufacturer’s warranty terms; ENORPA provides coordination.

How are documentation and conformity requirements determined?

The product’s operating conditions, configuration and project requirements form the basis of the assessment. The applicable documentation and scope of conformity are clarified in the order’s technical file.

How is technical support provided abroad?

Depending on the project and country conditions, local teams working under ENORPA supervision may be considered. A contracted local service provider or a technical team from Türkiye is assigned according to the nature of the fault. Service terms are defined in the contract.

Is an economizer included in the delivery?

An economizer is not assumed to be included as standard. Its suitability for the fuel and operating conditions is assessed, and any selected heat recovery equipment is listed separately in the technical proposal.

SAME PRODUCT FAMILY

Explore other air heating solutions.

FREE CONSULTATION

Let’s plan your HAS project together.

Share your requirements with our engineers. Let’s clarify the fuel, capacity, site conditions and scope of supply together.

We can start with this information, if available

  • Heat demand · kcal/h
  • Airflow · m³/h
  • Target outlet air temperature · °C
  • Solid fuel type and properties

If you do not know the exact values, we can clarify your requirements together.