LIQUID/GAS-FUELLED STEAM BOILER

Kuvars NG.

Continuous steam generation with liquid and gas fuels for demanding operating conditions.

Steam output range500–20,000 kg/h
Operating pressure1–16 barG
FuelLiquid / gas fuel
Manufacturing standardEN 12953
DESIGN APPROACH

We design your boiler room as a complete system.

For Kuvars NG, we assess your process steam requirements, operating pressure and daily load variations together. We design the boiler as part of a coordinated boiler room, integrating fuel preparation, combustion air, feedwater, steam distribution and the flue system.

We select the burner, fuel preparation equipment and supply pipework to suit the properties of the liquid or gaseous fuel. The design accounts for the burner’s air requirements, boiler room ventilation and flue operating conditions. Fuel types and any backup fuel arrangements depend on the selected burner and system equipment.

We engineer feedwater treatment, pumping, steam discharge, condensate return and the necessary drain and blowdown lines together with the process installation. We ensure that water level and pressure control equipment is compatible with the boiler and feedwater system. Water quality, scale prevention and corrosion control form part of the operating plan.

The layout accounts for maintenance door opening, service clearances, ventilation and operator access to the controls. This allows us to plan the system as a whole, from installation through operation and maintenance. Final capacity, equipment selection and scope of supply are determined for each project and order.

Fully cylindricalScotch typeThree-passFire-tube

Boiler room equipment

Click a number in the drawing to see the equipment name.
Kuvars NG boiler room · Front-left isometric view 3. Main steam outlet valve 3 4. Lifting lug 4 5. Manhole 5 6. Lifting lug 6 1. Safety valve 1 2. Safety valve 2 7. Pressure gauges 7 8. Pressure switches 8 9. Pressure sensor 9 10. Temperature sensor 10 11. Pressure manifold air vent valve 11 12. Vacuum breaker 12 13. Pressure manifold 13 14. Level chamber 14 15. Magnetic level indicators 15 16. Level measurement sensor 16 17. Front doors 17 18. Burner 18
Kuvars NG boiler room layout. Equipment and scope of supply are determined for each project.

Boiler room equipment

Click a number in the drawing to see the equipment name.
Kuvars NG boiler room · Front-left isometric view 3. Main steam outlet valve 3 4. Lifting lug 4 5. Manhole 5 6. Lifting lug 6 1. Safety valve 1 2. Safety valve 2 7. Pressure gauges 7 8. Pressure switches 8 9. Pressure sensor 9 10. Temperature sensor 10 11. Pressure manifold air vent valve 11 12. Vacuum breaker 12 13. Pressure manifold 13 14. Level chamber 14 15. Magnetic level indicators 15 16. Level measurement sensor 16 17. Front doors 17 18. Burner 18
FUEL FEEDING & COMBUSTION

An operating arrangement
suited to your fuel.

  1. Preparation: Before starting, the burner checks the required safety conditions.
  2. Pre-purge: The fan supplies air to the combustion chamber to remove any combustible gases that may remain inside.
  3. Ignition preparation: Airflow is adjusted for ignition, and a spark is generated between the electrodes.
  4. Fuel supply: Gaseous fuel is delivered to the combustion head, or liquid fuel is atomized into fine droplets through the nozzle.
  5. Fuel–air mixing: The fuel combines with combustion air supplied by the fan, creating conditions suitable for ignition.
  6. Ignition: The spark ignites the fuel, producing a controlled flame in the combustion chamber.
  7. Continuous combustion: The burner maintains stable combustion by adjusting fuel and air quantities to the boiler’s requirements.
  8. Shutdown: Fuel supply is cut off to extinguish the flame, and the burner stops after the fan completes the post-purge.

These stages may vary according to the burner’s manufacturer and model. This description explains the general operating principle.

TECHNICAL SPECIFICATIONS

Capacity, pressure and boiler construction.

Kuvars NG is designed for steam generation with a fully cylindrical, Scotch-type, three-pass, fire-tube construction. Capacity and equipment selection are engineered around the facility’s operating conditions.

Kuvars NG technical specifications

Capacity and construction

Steam output range500–20,000 kg/h
Operating pressure1–16 barG
ConstructionFully cylindrical · Scotch type · Three-pass · Fire-tube
FuelLiquid / gas fuel
Fuel feeding / combustionBurner selected for the order
ManufacturingEngineered to order
Product familySteam Boilers & Generators

Material standards

Boiler steels In high-pressure sections:EN 10028-2 grade P355GH, P295GH, P265GH and P235GH
Steel grades In non-pressurized or low-pressure sections:EN 10025-2 grade S355JR, S235JR
Fire and smoke tubesEN 10217-2 or EN 10216-2 grade P235GH

The stated ranges are the limits of the product series; they do not represent the load adjustment range of a single unit. Final capacity, operating conditions and equipment scope are determined for each project and order.

Fuel and combustion

Liquid or gaseous fuel is delivered to the burner through a supply line suited to that fuel. Gas supply pressure and flow rate, and liquid fuel storage and flow characteristics, are assessed alongside burner selection. Filtration, regulation and any necessary fuel preparation equipment are determined for each project. A single burner must not be assumed to operate with every fuel.

At startup, safety conditions are checked and the combustion chamber is pre-purged. The burner fan supplies combustion air. Gaseous fuel is delivered to the combustion head, while liquid fuel is atomized and mixed with air.

Combustion is monitored by the flame supervision system. Fuel and air quantities are adjusted according to the burner’s control method and heat demand. During shutdown, fuel supply is cut off and post-purge is completed according to the burner’s control sequence.

Heat transfer and steam generation

Hot gases are directed through the three-pass fire-tube arrangement by the reversal sections, transferring energy to the boiler water. Cleaning the flue gas passages, checking deposits on heat transfer surfaces and providing maintenance access form part of the operating plan.

After heat transfer, the gases flow towards the flue connection. Flue and duct dimensions, gas flow rate and pressure losses are assessed together.

Boiler water turns into steam at the boiling temperature corresponding to the operating pressure. Steam is supplied to the process line, and the feedwater system replenishes the water used. Pressure and feedwater control and safety equipment are arranged according to the design.

Water treatment, condensate return and drain and blowdown arrangements are engineered around site conditions. Feedwater quality is important for controlling scale and corrosion. Operation and maintenance must follow the product’s instructions.

Insulation and maintenance

Hot surfaces are protected with insulation and external cladding to limit heat loss. Materials, insulation thickness and cladding details are determined by the operating temperature and order scope.

Maintenance access is provided to the combustion system, heat transfer surfaces and flue connections. Service clearances, door opening directions and cleaning areas are considered in the facility layout.

FUEL COMPATIBILITY

The right configuration
starts with your fuel.

With an appropriate burner and fuel preparation system, Kuvars NG can use natural gas (NG), compressed natural gas (CNG), liquefied natural gas (LNG), propane (LPG), methane, biogas, fuel oil, diesel, light fuel oil and heavy fuel oil.

For methane and biogas, gas composition, treatment requirements and burner compatibility are assessed separately. A single burner must not be assumed to support every fuel.

Fuels may be used individually. With a suitable system configuration, two or three different fuels may also be considered as backup alternatives to one another. Fuel types and combinations are specified together with the burner and system configuration when the order is placed.

Natural gas / LNG / CNGLPGDiesel / Fuel oilMethaneBiogas
Open the unit converter
LIQUID / GASEOUS FUELS · IEA · LOWER HEATING VALUE41.57–50.03 MJ/kg

When lower heating value changes, capacity may change too

All other conditions being equal, more of a fuel with a lower heating value must be burned to meet the same heat demand. This affects fuel feeding, the combustion chamber, heat transfer surfaces and, at the design stage, boiler dimensions.

At ENORPA, we design the boiler around the selected fuel and target capacity. An existing boiler cannot deliver the same thermal output with every fuel. Achievable capacity is determined by assessing fuel properties, the burner or feeding system, and boiler design together.

Explore the heating values of different fuels
ENORPA 360° SUPPORT

From the first conversation throughout your equipment’s life.

We identify your needs together
and support you at every stage.

360°
ENORPA
SUPPORT SHIELD

Comprehensive support in four stages.
One engineering approach.

01 ANALYSIS & CONSULTANCY

The right decision
starts with an expert.

Speak directly with our specialist engineers and receive free advice. Let’s analyse your needs together and identify the right product and capacity for you.

02 CUSTOM MANUFACTURING & SUPPLY

Tailored to your needs.
Built for you.

Let’s turn your technical requirements into equipment made for you. We manufacture and supply your product and the necessary equipment to meet your specific needs.

03 INSTALLATION & COMMISSIONING

We install it. Get it running.
Prepare your team.

We install and commission the products you purchase from us, then train your personnel in their use and operation.

04 LIFETIME TECHNICAL SUPPORT

As your equipment keeps working,
our support continues.

When a fault occurs, we support you through our contracted local service providers or a technical team dispatched from our headquarters, depending on the nature of the issue. We provide technical support throughout the life of your equipment.

FREQUENTLY ASKED QUESTIONS

Before you
decide.

Can Kuvars NG be manufactured for an intermediate capacity?

Within the series’ steam output range of 500–20,000 kg/h, a suitable capacity is engineered by assessing your requirements, fuel and operating conditions together.

Which feeding or combustion system is used?

A burner is selected for the order. Kuvars NG is a burner-fired boiler for liquid/gas fuels. It does not have a solid-fuel grate.

Which equipment is included in the delivery?

You can choose the boiler body alone, supply with auxiliary equipment, or a solution covering the boiler room. Whether the burner, feeding system, control panel, pumps, fans, flue and other equipment are included is specified individually in the technical proposal.

Are installation and personnel training provided?

Installation, electrical and automation connections, commissioning and operator training are planned according to the project’s service scope. The boundaries of the work are defined in the technical proposal and contract.

When does the warranty begin?

ENORPA-manufactured products carry a 24-month warranty against manufacturing defects. The warranty starts on the actual commissioning date accepted by ENORPA, but no later than two calendar months after delivery. Third-party equipment is subject to the relevant manufacturer’s warranty terms; ENORPA provides coordination.

How are documentation and conformity requirements determined?

The product’s operating conditions, configuration and project requirements form the basis of the assessment. The applicable documentation and scope of conformity are clarified in the order’s technical file.

How is technical support provided abroad?

Depending on the project and country conditions, local teams working under ENORPA supervision may be considered. A contracted local service provider or a technical team from Türkiye is assigned according to the nature of the fault. Service terms are defined in the contract.

Is an economizer included in the delivery?

An economizer is not assumed to be included as standard. Its suitability for the fuel and operating conditions is assessed, and any selected heat recovery equipment is listed separately in the technical proposal.

SAME PRODUCT FAMILY

Explore other steam solutions.

FREE CONSULTATION

Let’s plan your Kuvars NG project together.

Discuss the capacity, fuel system and scope of supply suited to your facility with our engineers.

We can start with this information, if available

  • Steam requirement · kg/h
  • Operating pressure · barG
  • Fuel you plan to use

If you do not know the exact values, we can clarify your requirements together.